|Power Reactor                                    |Event Number:   38602       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: CRYSTAL RIVER            REGION:  2  |NOTIFICATION DATE: 01/01/2002|
|    UNIT:  [3] [] []                 STATE:  FL |NOTIFICATION TIME: 10:08[EST]|
|   RXTYPE: [3] B&W-L-LP                         |EVENT DATE:        01/01/2002|
+------------------------------------------------+EVENT TIME:        09:19[EST]|
| NRC NOTIFIED BY:  BILL BANDHAUER               |LAST UPDATE DATE:  08/20/2002|
|  HQ OPS OFFICER:  FANGIE JONES                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |ANNE BOLAND          R2      |
|10 CFR SECTION:                                 |                             |
|APRE 50.72(b)(2)(xi)     OFFSITE NOTIFICATION   |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE  
|
+-----+----------+-------+--------+-----------------+--------+-----------------+
|3     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| OFFSITE NOTIFICATION DUE RESCUED SEA TURTLE                                  |
|                                                                              |
| EN #37902 started the biennial report period.                                |
|                                                                              |
| On January 1, 2002 at 0919, a rescued sea turtle was identified as a green   |
| sea turtle.  This is the 62nd rescue of a live sea turtle at Crystal River   |
| Unit 3 (CR-3) in this biennial period. Notification to the National Marine   |
| Fisheries Service and the Florida Fish and Wildlife Conservation Commission. |
|                                                                              |
|                                                                              |
| The licensee intends to notify the NRC Resident Inspector.                   |
|                                                                              |
| * * *  UPDATE ON 1/05/02 @ 1002 BY RAWLS TO GOULD  * * *                     |
|                                                                              |
| On January 5, 2002, at 0720, a rescued sea turtle was identified as a        |
| Loggerhead Sea Turtle. This is the 63rd rescue of a live sea turtle at       |
| Crystal River Unit 3 (CR3) in this biennial period.  This is reportable as a |
| 4-hour report under 10 CFR 50.72(b)(2)(xi) as this event is related to the   |
| protection of the environment for which a notification to other government   |
| agencies (National Marine Fisheries Service and Florida Fish and Wildlife    |
| Conservation Commission) has been or will be made.                           |
|                                                                              |
| The NRC Resident Inspector was notified.                                     |
|                                                                              |
| Reg 2 RDO (Decker) was notified.                                             |
|                                                                              |
| * * * UPDATE ON 01/09/02 @ 1107 EST BY ANDY BARNES TAKEN BY MACKINNON * * *  |
|                                                                              |
| On January 9, 2002, at 0838, a rescued sea turtle was identified as a Kemp's |
| Ridley Sea Turtle. This is the 64th rescue of a live turtle at Crystal River |
| Unit 3 (CR-3) in this biennial period. This is reportable as a 4-hour 10 CFR |
| 50.72(b)(2)(xi) as this event is related to the protection of the            |
| environment for which a notification to other government agencies (National  |
| Marine Fisheries Service and Florida Fish and Wildlife Conservation          |
| Commission) has been or will be made.                                        |
|                                                                              |
| The NRC Resident Inspector was notified.                                     |
|                                                                              |
| Reg 2 (Brian Bonser) was notified.                                           |
|                                                                              |
| * * * UPDATE ON 02/17/02 at 0940 EST BY RICKY RAWLS TO FANGIE JONES * * *    |
|                                                                              |
| "On February 17, 2002 at 0820, a rescued injured sea turtle was identified   |
| as a Kemp's Ridley Sea Turtle. The injury will require transportation to     |
| Clearwater Marine Science Center or Florida Fish and Wildlife Conservation   |
| Refuge. The Injury appears to be from a boat propeller. This is the 65th     |
| rescue of a live sea turtle at Crystal River Unit 3 (CR-3) in this biennial  |
| period. This is Reportable as a 4-Hour Report under 10 CFR 50.72(b)(2)(xi)   |
| as this event is related to the protection of the environment for which a    |
| notification to other government agencies (National Marine Fisheries Service |
| and Florida Fish and Wildlife Conservation Commission) has been or will be   |
| made. This Is an update to event 38602."                                     |
|                                                                              |
| The NRC Resident Inspector will be notified.  R2DO (Stephen Cahill) has been |
| notified.                                                                    |
|                                                                              |
| * * * UPDATE ON 03/01/02 AT 1122 EST BY RICKY RAWLS TO GERRY WAIG * * *      |
|                                                                              |
| "On March 1, 2002 at 0952, a healthy rescued sea turtle was identified as a  |
| Green Sea Turtle. This is the 66th rescue of a live sea turtle at Crystal    |
| River Unit 3 (CR-3) in this biennial period. This is Reportable as a 4-Hour  |
| Report under 10 CFR 50.72(b)(2)(xi) as this event is related to the          |
| protection of the environment for which a notification to other government   |
| agencies (National Marine Fisheries Service and Florida Fish and Wildlife    |
| Conservation Commission) has been or will be made. This is an update to      |
| event 38602."                                                                |
|                                                                              |
| The NRC Resident Inspector was notified. R2DO (Julian) was notified.         |
|                                                                              |
| * * * UPDATE ON 03/07/02 AT 1114 EST BY CHUCK MORRIS TO MIKE NORRIS * * *    |
|                                                                              |
| "On March 7, 2002 at 0835, two healthy sea turtles rescued at CR#3 were      |
| identified as Green Sea Turtles. These are the 67th and 68th live sea turtle |
| rescues at the Crystal River Energy Complex in this biennial period. This is |
| Reportable as a 4-Hour Report under 10 CFR 50.72(b)(2)(xi) as this event is  |
| related to the protection of the environment for which a notification to     |
| other government agencies (National Marine Fisheries Service and Florida     |
| Fish and Wildlife Conservation Commission) has been or will be made. This is |
| an update to event 38602."                                                   |
|                                                                              |
| The NRC Resident Inspector was notified. R2DO (Henson) was notified.         |
|                                                                              |
| * * * UPDATE ON 04/02/02 at 0408 EST BY RICKY RAWLS TO FANGIE JONES * * *    |
|                                                                              |
| "On April 2, 2002 at 0236, two sea turtles previously rescued at CR#3 intake |
| area were identified by FPC Mariculture staff as Kemp Ridley Sea Turtles.    |
| One of the turtles appears to be in distress and may require transportation  |
| to Clearwater Marine Science Center of Florida Fish and Wildlife             |
| Conservation Refuge. These are the 69th and 70th live sea turtle rescues at  |
| the Crystal River Energy Complex in this biennial period. This is Reportable |
| as a 4-Hour Report under 10 CFR 50.72(b)(2)(xi) as this event is related to  |
| the protection of the environment for which a notification to other          |
| government agencies (National Marine Fisheries Service and Florida Fish and  |
| Wildlife Conservation Commission) has been or will be made. This is an       |
| update to event 38602."                                                      |
|                                                                              |
| The NRC Resident Inspector will be notified.  The R2DO (Carolyn Evans) was   |
| notified.                                                                    |
|                                                                              |
| ***** UPDATE AT 1023 EDT ON 05/19/02 FROM PELLERIN TO LEIGH TROCINE *****    |
|                                                                              |
| The following text is a portion of a facsimile received from the licensee:   |
|                                                                              |
| "On May 19, 2002, at 0916, a sea turtle previously rescued at CR#3 intake    |
| area was identified by FPC Mariculture staff as Green Sea Turtle.  This is   |
| the 71st live sea turtle rescue at the Crystal River Energy Complex in this  |
| biennial period.  This is Reportable as a 4-Hour Report under 10 CFR         |
| 50.72(b)(2)(xi) as this event is related to the protection of the            |
| environment for which a notification to other government agencies (National  |
| Marine Fisheries Service and Florida Fish and Wildlife Conservation          |
| Commission) has been or will be made.  This is an update to event 38602."    |
|                                                                              |
| The licensee plans to notify the National Marine Fisheries Service and       |
| Florida Fish and Wildlife Conservation Commission and the NRC resident       |
| inspector.  The NRC operations officer notified the R2DO (Paul               |
| Fredrickson).                                                                |
|                                                                              |
| * * * UPDATE 1816 EDT ON 5/28/02 FROM BERRY FOSTER TO S. SANDIN * * *        |
|                                                                              |
| "On May 28, 2002 at 1700, a sea turtle previously rescued at CR#3 intake     |
| area was identified by FPC Mariculture staff as a Green Sea Turtle. This is  |
| the 72nd live sea turtle rescue at the Crystal River Energy Complex in this  |
| biennial period. The turtle is being transported to the Clearwater Marine    |
| Science Center. This is Reportable as a 4-Hour Report under 10 CFR 50.72 (b) |
| (2) (xi) as this event is related to the protection of the environment for   |
| which a notification to other government agencies (National Marine Fisheries |
| Service and Florida Fish and Wildlife Conservation Commission) has been or   |
| will be made. This is an update to event 38602."                             |
|                                                                              |
| The licensee will inform the NRC Resident Inspector.  Notified               |
| R2DO(Landis).                                                                |
|                                                                              |
| * * * UPDATE 1602 EDT ON 5/31/02 FROM BILL BANDHAUER TO MIKE NORRIS * * *    |
|                                                                              |
| "On May 30, 2002 at 1323, a sea turtle previously rescued at CR#3 intake     |
| area was identified by FPC Mariculture staff as a Kemp's Ridley Sea Turtle.  |
| This is the 72nd live sea turtle rescue at the Crystal River Energy Complex  |
| in this biennial period. (Note: The sequential numbering of the live sea     |
| turtle takes has been modified to reflect the actual live sea turtle takes,  |
| On 4/02/02, a live rescue of two turtles was reported, however, one of the   |
| turtles died and was reclassified as a non-causal mortality, which is        |
| non-reportable). This event is Reportable as a 4-Hour Report under 10 CFR    |
| 50.72(b) (2) (xi) as this event is related to the protection of the          |
| environment for which a notification to other government agencies (National  |
| Marine Fisheries Service and Florida Fish and Wildlife Conservation          |
| Commission) has been or will be made. This is an update to event 38602."     |
|                                                                              |
| The NRC Resident Inspector has been notified.  Notified R2DO (Landis).       |
|                                                                              |
| *****UPDATE AT 13:58 EDT ON 7/18/02 FROM SWEENEY TO LAURA*****               |
|                                                                              |
| An offsite notification to the State regarding a green sea turtle that was   |
| rescued from the CR#3 intake area by the FPC Mariculture staff.              |
|                                                                              |
| The NRC resident inspector was notified.  Notified R2DO (C. Payne).          |
|                                                                              |
| * * * UPDATE 1126 EDT ON 8/1/02 FROM BILL BANDHAUER TO FANGIE JONES * * *    |
|                                                                              |
| "At 0915 on August 1,2002, a dead sea turtle recovered at the CR#3 intake    |
| area was identified by FPC Mariculture staff as a Kemps Ridley Turtle. FPC   |
| determined that the cause of death was non-causally related to the operation |
| of CR3. This is the 7th dead Kemps Ridley Turtle recovery at the Crystal     |
| River Energy Complex in this biennial period. The threshold for reporting    |
| non-causal sea turtle deaths is 6 in a biennial period. This event is        |
| Reportable as a 4-Hour Report under 10 CFR 50.72 (b) (2) (xi) as this event  |
| is related to the protection of the environment for which a notification to  |
| other government agencies (National Marine Fisheries Service and Florida     |
| Fish and Wildlife Conservation Commission) will be made. This is an update   |
| to event 38602."                                                             |
|                                                                              |
| The licensee intends to notify the NRC Resident Inspector.  The R2DO (Mike   |
| Ernstes) has been notified.                                                  |
|                                                                              |
| * * * UPDATE 1529 EDT ON 8/8/02 FROM DAN DeBOER TO GERRY WAIG * * *          |
|                                                                              |
| "At 1234 on August 8, 2002, FPC determined that the dead Kemps-Ridley sea    |
| turtle recovered at 1930 on May 11, 2002, at the Crystal River Unit 3 intake |
| area was reportable as a 4-Hour Report under 10 CFR 50.72 (b) (2) (xi). This |
| event is related to the protection of the environment for which a            |
| notification to other government agencies (National Marine Fisheries Service |
| and Florida Fish and Wildlife Conservation Commission) has been made. At     |
| 1347 on May 13, 2002 the FPC Mariculture Center determined that the cause of |
| death was non-causally related to the operation of Crystal River Unit 3.     |
| This was the 6th non-causal dead turtle recovery at the Crystal River Energy |
| Complex in this biennial period. The threshold for reporting non-causal sea  |
| turtle deaths is 6 in a biennial period. This is an update to event 38602."  |
|                                                                              |
| The licensee notified the NRC Resident Inspector. The R2DO (Claude Julian)   |
| has been notified.                                                           |
|                                                                              |
| ***UPDATE 11:10 EDT ON 8/20/02 FROM McCallum to LAURA***                     |
|                                                                              |
| "On August 20, 2002 at 0932, a sea turtle previously rescued at CR#3 intake  |
| area was identified by FPC Mariculture staff as a Kemp's Ridley Sea Turtle.  |
| This is the 74th live sea turtle rescue at the Crystal River Energy Complex  |
| in this biennial period. This event is Reportable as a 4-Hour Report under   |
| 10 CFR 50.72(b) (2) (xi) as this event is related to the protection of the   |
| environment for which a notification to other government agencies (National  |
| Marine Fisheries Service and Florida Fish and Wildlife Conservation          |
| Commission) has been or will be made. This is an update to event 38602."     |
|                                                                              |
| The licensee notified the NRC Resident Inspector.  The R2DO (M. LESSER) has  |
| been notified.                                                               |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|General Information or Other                     |Event Number:   39134       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG:  MA RADIATION CONTROL PROGRAM         |NOTIFICATION DATE:
08/16/2002|
|LICENSEE:  BRISTOL-MYERS SQUIBB MEDICAL IMAGING |NOTIFICATION TIME:
11:02[EDT]|
|    CITY:  BILLERICA                REGION:  1  |EVENT DATE:        08/14/2002|
|  COUNTY:                            STATE:  MA |EVENT TIME:             [EDT]|
|LICENSE#:  60-0088               AGREEMENT:  Y  |LAST UPDATE DATE:  08/16/2002|
|  DOCKET:                                       |+----------------------------+
|                                                |PERSON          ORGANIZATION |
|                                                |GLENN MEYER          R1      |
|                                                |C.W. (BILL) REAMER   NMSS    |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  KENATH TRAEGDE               |                             |
|  HQ OPS OFFICER:  FANGIE JONES                 |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          NON EMERGENCY         |                             |
|10 CFR SECTION:                                 |                             |
|NAGR                     AGREEMENT STATE        |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| AGREEMENT STATE REPORT - PERSONNEL OVER EXPOSURE                             |
|                                                                              |
| "Cyclotron chemistry technician received 4.56 rem TEDE in one week.  The     |
| worker's exposure for the calendar year is now 5.79 rem.  The cause of the   |
| additional exposure is related to work performed directly with cyclotron     |
| target material.  This exposure was incurred over a period of one week.  The |
| details of the event are under investigation."                               |
|                                                                              |
| The exposure took place the week of July 28 to August 4, 2002.               |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   39139       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: WOLF CREEK               REGION:  4  |NOTIFICATION DATE: 08/20/2002|
|    UNIT:  [1] [] []                 STATE:  KS |NOTIFICATION TIME: 16:50[EDT]|
|   RXTYPE: [1] W-4-LP                           |EVENT DATE:        08/20/2002|
+------------------------------------------------+EVENT TIME:        10:30[CDT]|
| NRC NOTIFIED BY:  STEVEN A. HENRY              |LAST UPDATE DATE:  08/20/2002|
|  HQ OPS OFFICER:  MIKE NORRIS                  +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |WILLIAM JOHNSON      R4      |
|10 CFR SECTION:                                 |                             |
|AUNA 50.72(b)(3)(ii)(B)  UNANALYZED CONDITION   |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE  
|
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| UNANALYZED CONDITION FOR POST FIRE SAFE SHUTDOWN                             |
|                                                                              |
| "On August 20, 2002, conditions were discovered where a postulated fire      |
| could cause the loss of both Centrifugal Charging Pumps (CCP) capability to  |
| successfully inject borated water to the reactor and to keep the Reactor     |
| Coolant Pump (RCP) seals cool. Wolf Creek is in Mode 1, at 100% power.       |
|                                                                              |
| "During reviews associated with post fire safe shutdown reanalysis work,     |
| Wolf Creek personnel discovered that power and control cables for both CCP   |
| train minimum flow valves, both train CCP discharge valves to the RCP seals, |
| and both train CCP suction valves from the Volume Control Tank (VCT) and     |
| Refueling Water Storage Tank (RWST) are routed in electrical raceways in the |
| same fire area with intervening combustibles between the two redundant       |
| trains. This does not meet our commitments to 10CFR50 Appendix R.lll.G as    |
| reflected in our approved Fire Protection Plan.                              |
|                                                                              |
| "Following a fire In the plant that requires a plant shutdown, the function  |
| of the CCP is to inject borated water into the reactor to maintain reactor   |
| water inventory, maintain shutdown reactivity margin, and to maintain a      |
| cooling water flow to the RCP seals to prevent damage to the seals. A fire   |
| in this fire area has the potential to cause the above-mentioned valves to   |
| not function properly and cause a loss of the capability to borate, maintain |
| inventory, and to cool the RCP seals.                                        |
|                                                                              |
| "Based on the guidance provided in NUREG 1022, Revision 2, this situation    |
| meets the criterion of 10CFR50.72(b)(3)(ii)(B) for an 8-hour ENS             |
| notification, as it relates to being in an unanalyzed condition.             |
|                                                                              |
| "The licensee has previously implemented a 1-hour fire watch in this fire    |
| area."                                                                       |
|                                                                              |
| The NRC Resident Inspector has been notified.                                |
+------------------------------------------------------------------------------+
