Event Notification Report for October 29, 2001

                         
                    U.S. Nuclear Regulatory Commission
                              Operations Center

                              Event Reports For
                           10/26/2001 - 10/29/2001

                              ** EVENT NUMBERS **

37902  38380  38426  38429  38430  38431  38432  38433  38435  
.
+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   37902       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: CRYSTAL RIVER            REGION:  2  |NOTIFICATION DATE: 04/09/2001|
|    UNIT:  [3] [] []                 STATE:  FL |NOTIFICATION TIME: 11:08[EDT]|
|   RXTYPE: [3] B&W-L-LP                         |EVENT DATE:        04/09/2001|
+------------------------------------------------+EVENT TIME:        09:54[EDT]|
| NRC NOTIFIED BY:  RICHARD SWEENEY              |LAST UPDATE DATE:  10/28/2001|
|  HQ OPS OFFICER:  STEVE SANDIN                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |CAUDLE JULIAN        R2      |
|10 CFR SECTION:                                 |                             |
|APRE 50.72(b)(2)(xi)     OFFSITE NOTIFICATION   |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE  
|
+-----+----------+-------+--------+-----------------+--------+-----------------+
|3     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| OFFSITE NOTIFICATION TO THE NATIONAL MARINE AND FISHERIES SERVICE AS A      
|
| RESULT OF THE ENDANGERED SEA TURTLES NON-LETHAL TAKE LIMIT BEING
EXCEEDED    |
|                                                                              |
| "On April 09, 2001 at 0940 the 40th non-lethal sea turtle take in the        |
| biennial period occurred.                                                    |
|                                                                              |
| "In accordance with Crystal River Unit #3 Operating License, Appendix B,     |
| Environmental Protection Plan (Non-Radiological),  'Endangered or threatened |
| sea turtles shall be protected in accordance with the Incidental Take        |
| Statement issued by the National Marine and Fisheries Service (NMFS).'  The  |
| NMFS has established numerical limits on live takes, lethal takes causally   |
| related to plant operation, and lethal takes not related to plant            |
| operations.                                                                  |
|                                                                              |
| "The NMFS must be notified within five days whenever:                        |
|                                                                              |
| a.  The 40th non-lethal take occurs in the biennial period, or               |
| b.  The third causally related mortality occurs in the biennial period, or   |
| c.   The sixth non-causally related mortality occurs in the biennial         |
| period.                                                                      |
|                                                                              |
| "The current biennial period for monitoring sea turtle takes began January   |
| 1, 2001.                                                                     |
|                                                                              |
| "Thus, in accordance with Crystal Unit #3 Administrative Instruction 571,    |
| Sea Turtle Rescue and Handling Guidance, the NMFS must be notified within    |
| five days.                                                                   |
|                                                                              |
| "In accordance with Crystal River Unit #3 Compliance Procedure 151, External |
| Reporting Requirements, this 40th non-lethal sea turtle take is Reportable   |
| as a 4-Hour Report under 10 CFR 50.72(b)(2)(xi) as this event is related to  |
| the protection of the environment for which a notification to other          |
| government agencies has been or will be made."                               |
|                                                                              |
| The licensee will inform the NRC resident inspector.                         |
|                                                                              |
| * * * UPDATE 0944EDT ON 4/10/01 FROM R. SWEENEY TO S. SANDIN * * *           |
|                                                                              |
| "On April 10, 2001 at 0859 the 41st non-lethal sea turtle take in the        |
| biennial period occurred."                                                   |
|                                                                              |
| The licensee informed the NRC resident inspector.  Notified R2DO(Julian).    |
|                                                                              |
| ***** UPDATE RECEIVED AT 0911 ON 04/17/01 FROM CHRISTOPHER PELLERIN TO
LEIGH |
| TROCINE *****                                                                |
|                                                                              |
| The 42nd, non-lethal, sea turtle take in the biennial period occurred at     |
| 0810 on April 17, 2001.                                                      |
|                                                                              |
| The licensee notified the NRC resident inspector.  The NRC operations        |
| officer notified the R2DO (Ernstes).                                         |
|                                                                              |
| * * * UPDATE 1125 EDT ON 5/1/01 FROM DAVID SCHULKER TO FANGIE JONES * * *    |
|                                                                              |
| "On May 1, 2001 at 0805 a turtle was identified as the 43rd rescued, live    |
| sea turtle in this biennial period.  This sea turtle will be kept for a      |
| short observation period and then safely returned to the environment."       |
|                                                                              |
| The licensee will inform the NRC Resident Inspector and the National         |
| Wildlife and Fisheries Service.  Notified R2DO(Jay Henson).                  |
|                                                                              |
| * * * UPDATE ON 5/29/01 BY FERGUSON TO SANDIN * * *                          |
|                                                                              |
| On May 29, 2001 at 0943 two turtles were identified as the 44th and 45th     |
| rescued, live Sea turtles in this biennial period. These healthy sea turtles |
| will be kept for a short observation period and then safely returned to the  |
| environment.                                                                 |
|                                                                              |
| This is Reportable as a 4-Hour Report under 10 CFR 50.72 (b) (2) (xi) as     |
| this event is related to the protection of the environment for which a       |
| notification to other government agencies has been or will be made. This is  |
| an update to event 37902.                                                    |
|                                                                              |
| The NRC Resident Inspector was notified.  The REG2 RDO(Barr) was informed.   |
|                                                                              |
| * * * UPDATE 2014 EDT 6/4/2001 FROM RAWLS TAKEN BY STRANSKY * * *            |
|                                                                              |
| On June 4, 2001 at 1815, the 46th non-lethal sea turtle (Kemp's Ridley) take |
| in the biennial period occurred. The license has informed the NRC resident   |
| inspector.  Notified R2DO (Barr).                                            |
|                                                                              |
| * * * UPDATE 1315EDT ON 6/10/01 FROM CHARLES J. MORRIS TO S. SANDIN * * *    |
|                                                                              |
| On June 10, 2001 at 1100, the 47th non-lethal sea turtle take in the         |
| biennial period occurred. The license has informed the NRC resident          |
| inspector.  Notified R2DO (Bonser).                                          |
|                                                                              |
| * * * UPDATE 0952 ON 8/20/2001 FROM FERGUSON TAKEN BY STRANSKY * * *         |
|                                                                              |
| On August 20, 2001 at 0815, the 48th non-lethal sea turtle take in the       |
| biennial period occurred. The licensee as informed the NRC resident          |
| inspector. Notified R2DO (Payne).                                            |
|                                                                              |
| * * *  UPDATE 1216 ON 9/3/01 BY SCHULKER TO GOULD * * *                      |
|                                                                              |
| On September 3, 2001 at 0845 a turtle was identified as the 49th rescued,    |
| live sea turtle in this biennial period.  This turtle has an injury to the   |
| lower jaw and is being transported to the Clearwater Marine Science Station  |
| for treatment. It has not been determined at this time if the injury is      |
| casually related to Crystal River Operations.                                |
|                                                                              |
| This is Reportable as a 4-Hour Report under 10 CFR 50.72 (b) (2) (xi) as     |
| this event is related to the protection of the environment for which a       |
| notification to other government agencies has been or will be made. This is  |
| an update to event 37902.                                                    |
|                                                                              |
| The NRC Resident Inspector and  other government agencies will be notified.  |
|                                                                              |
| Notified Reg 2 RDO(Lesser)                                                   |
|                                                                              |
| *****  UPDATE FROM RICHARD SWEENEY TO LEIGH TROCINE AT 0910 ON 10/28/01      |
| *****                                                                        |
|                                                                              |
| The following text is a portion of a facsimile received from the licensee:   |
|                                                                              |
| "On October 28, 2001, at 0030, a turtle was identified as the 50th rescued,  |
| live sea turtle in this biennial period.  This is Reportable as a 4-Hour     |
| Report under 10 CFR 50.72(b)(2)(xi) as this event is related to the          |
| protection of the environment for which a notification to other government   |
| agencies has been or will be made."                                          |
|                                                                              |
| The licensee plans to notify the national Marine and Fishery Services and    |
| the NRC resident inspector.  The NRC operations officer notified the Region  |
| 2 Incident Response Center (McCree).                                         |
+------------------------------------------------------------------------------+
.
!!!!!!!!! THIS EVENT HAS BEEN RETRACTED. THIS EVENT HAS BEEN RETRACTED  !!!!!!!
+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   38380       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: FERMI                    REGION:  3  |NOTIFICATION DATE: 10/11/2001|
|    UNIT:  [2] [] []                 STATE:  MI |NOTIFICATION TIME: 17:56[EDT]|
|   RXTYPE: [2] GE-4                             |EVENT DATE:        10/11/2001|
+------------------------------------------------+EVENT TIME:        14:20[EDT]|
| NRC NOTIFIED BY:  GROFF                        |LAST UPDATE DATE:  10/26/2001|
|  HQ OPS OFFICER:  CHAUNCEY GOULD               +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |MICHAEL PARKER       R3      |
|10 CFR SECTION:                                 |                             |
|NONR                     OTHER UNSPEC REQMNT    |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE  
|
+-----+----------+-------+--------+-----------------+--------+-----------------+
|2     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| CONDITION OF LICENSE REPORT DUE TO UNAVAILABLE EMERGENCY LIGHTING           
|
|                                                                              |
| On October 11, 2001, following a fire protection program self assessment, it |
| was determined that emergency lighting was unavailable in two required       |
| locations.  Actions in these areas are required steps of procedure 20.000.18 |
| "Control of Plant from Dedicated Shutdown Panel."                            |
|                                                                              |
| The inability to perform steps in 20.000.18 constitutes a reportable         |
| condition under Fermi 2 License Condition 2.F as a violation of              |
| "Modifications for Fire Protection" as described in License Condition        |
| 2.C(9).                                                                      |
|                                                                              |
| Short term corrective action is to revise the procedure steps to obtain      |
| portable lighting prior to exiting the plant.  Long term corrective actions  |
| are being evaluated.                                                         |
|                                                                              |
| The NRC Resident Inspector was notified.                                     |
|                                                                              |
| * * * RETRACTION ON 10/26/01 AT 1315 ET REPORTED BY KEVIN DAHM TAKEN BY      |
| MACKINNON * * *                                                              |
|                                                                              |
| Upon further evaluation, it has been determined that  License Condition 2.C  |
| (9) was not violated.  The steps in question in the CTG 11-1 Control         |
| Building and in the EDG-11 Switchgear Room can be completed successfully     |
| with the current lighting configuration; and therefore, there is no adverse  |
| affect on the ability to achieve and maintain safe shutdown.  License        |
| Condition 2.C (9)  is thus met, and this condition is not reportable under   |
| License Condition 2.F.  The original notification, Event Number 38380, is    |
| retracted. R3DO (Brent Clayton) notified.                                    |
|                                                                              |
| The NRC Resident Inspector was notified of this retraction by the licensee.  |
+------------------------------------------------------------------------------+
.
+------------------------------------------------------------------------------+
|Other Nuclear Material                           |Event Number:   38426       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG:  TRAP ROCK INDUSTRIES                 |NOTIFICATION DATE: 10/25/2001|
|LICENSEE:  TRAP ROCK INDUSTRIES                 |NOTIFICATION TIME: 12:16[EDT]|
|    CITY:  EWING                    REGION:  1  |EVENT DATE:        10/24/2001|
|  COUNTY:                            STATE:  NJ |EVENT TIME:        22:30[EDT]|
|LICENSE#:  29-19707-01           AGREEMENT:  N  |LAST UPDATE DATE:  10/28/2001|
|  DOCKET:                                       |+----------------------------+
|                                                |PERSON          ORGANIZATION |
|                                                |R1 IRC TEAM MANAGER  R1      |
|                                                |BRAIN SMITH          NMSS    |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  WAYNE BYARD                  |                             |
|  HQ OPS OFFICER:  JOHN MacKINNON               |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          NON EMERGENCY         |                             |
|10 CFR SECTION:                                 |                             |
|BAB1 20.2201(a)(1)(i)    LOST/STOLEN LNM>1000X  |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| STOLEN TROXLER ASPHALT DENSITY GAUGE  CONTAINING 10 MILLICURIES OF           |
| CESIUM-137                                                                   |
|                                                                              |
| Prap Industries was performing work on a newly paved road which was closed   |
| to traffic at the intersection of Interstate 95 and Route 31 located in      |
| Ewing, NJ.   A Prap Rock Industries employee placed the Troxler gauge, Model |
| # 4640B, in a cart and moved the cart next to a tree and went off to perform |
| other duties.  When the person returned, time unknown how long the person    |
| was away from the unattained gauge, he discovered that the gauge and cart    |
| were missing.  This individual immediately notified the onsite New Jersey    |
| State Troopers that the gauge was missing.  A search of the area was         |
| conducted with not results in finding either the gauge or the cart.  NRC     |
| Region 1 individual was notified of this event by the licensee.              |
|                                                                              |
| ***** UPDATE AT 0740 ON 10/28/01 FROM NRR (KATHY GRAY) TO LEIGH TROCINE      |
| *****                                                                        |
|                                                                              |
| This event is being updated to correct the licensee's name.  It should have  |
| been Trap Rock Industries in lieu of Prap Rock Industries.                   |
+------------------------------------------------------------------------------+
.
+------------------------------------------------------------------------------+
|General Information or Other                     |Event Number:   38429       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG:  FLORIDA BUREAU OF RADIATION CONTROL  |NOTIFICATION DATE:
10/26/2001|
|LICENSEE:  BEISWENGER, HOCH & ASSOCIATES, INC.  |NOTIFICATION TIME:
08:55[EDT]|
|    CITY:  NORTH MIAMI              REGION:  2  |EVENT DATE:        10/26/2001|
|  COUNTY:                            STATE:  FL |EVENT TIME:             [EDT]|
|LICENSE#:  0759-1                AGREEMENT:  Y  |LAST UPDATE DATE:  10/26/2001|
|  DOCKET:                                       |+----------------------------+
|                                                |PERSON          ORGANIZATION |
|                                                |HAROLD CHRISTENSEN   R2      |
|                                                |FRED BROWN           NMSS    |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  MARK SEIDENSTICKER           |                             |
|  HQ OPS OFFICER:  FANGIE JONES                 |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          NON EMERGENCY         |                             |
|10 CFR SECTION:                                 |                             |
|NAGR                     AGREEMENT STATE        |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| AGREEMENT STATE REPORT - STOLEN TROXLER MOISTURE DENSITY GAUGE              
|
|                                                                              |
| A Troxler gauge was stored in an approved temporary storage site at a        |
| construction facility.  Overnight, several storage containers and offices    |
| were broken into.  The hasp of the storage container was broken and an       |
| additional door inside the container was forced and one of three gauges was  |
| stolen.  The police have been notified and a press release will be issued.   |
| The keys to the gauge were not at the temporary site and were not taken with |
| the gauge.                                                                   |
|                                                                              |
| The gauge is a Troxler model 3440, serial number 21218, with 8 mCi Cs-137    |
| and 40 mCi Am-241:Be sources.                                                |
+------------------------------------------------------------------------------+
.
+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   38430       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: TURKEY POINT             REGION:  2  |NOTIFICATION DATE: 10/26/2001|
|    UNIT:  [3] [4] []                STATE:  FL |NOTIFICATION TIME: 12:46[EDT]|
|   RXTYPE: [3] W-3-LP,[4] W-3-LP                |EVENT DATE:        10/26/2001|
+------------------------------------------------+EVENT TIME:        11:39[EDT]|
| NRC NOTIFIED BY:  MOWREY                       |LAST UPDATE DATE:  10/26/2001|
|  HQ OPS OFFICER:  JOHN MacKINNON               +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |R2 IRC TEAM MANAGER  R2      |
|10 CFR SECTION:                                 |                             |
|APRE 50.72(b)(2)(xi)     OFFSITE NOTIFICATION   |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE  
|
+-----+----------+-------+--------+-----------------+--------+-----------------+
|3     N          N       0        Hot Standby      |0        Hot Standby      |
|4     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| OFFSITE NOTIFICATION MADE TO FLORIDA FISH AND WILDLIFE CONSERVATION          |
| COMMISSION.                                                                  |
|                                                                              |
| A dead American crocodile hatchling discovered by plant access road, just    |
| outside employee parking lot.  The hatchling appears to have been struck by  |
| a vehicle. State of Florida Fish and Wildlife Conservation Commission has    |
| been notified.                                                               |
|                                                                              |
| The NRC Resident Inspector will be informed of this event notification by    |
| the licensee.                                                                |
+------------------------------------------------------------------------------+
.
+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   38431       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: FT CALHOUN               REGION:  4  |NOTIFICATION DATE: 10/26/2001|
|    UNIT:  [1] [] []                 STATE:  NE |NOTIFICATION TIME: 18:44[EDT]|
|   RXTYPE: [1] CE                               |EVENT DATE:        10/26/2001|
+------------------------------------------------+EVENT TIME:        16:00[CDT]|
| NRC NOTIFIED BY:  D. BANNISTER                 |LAST UPDATE DATE:  10/26/2001|
|  HQ OPS OFFICER:  JOHN MacKINNON               +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |WILLIAM JOHNSON      R4      |
|10 CFR SECTION:                                 |                             |
|HFIT 26.73               FITNESS FOR DUTY       |                             |
|                                                |                             |
|                                                |                     ----    |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE  
|
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| FITNESS FOR DUTY                                                             |
|                                                                              |
| A non-licensed supervisor employee was confirmed positive during a random    |
| drug test.  The employee's badge has been blocked.                           |
|                                                                              |
| Contact the HOO for further details.                                         |
|                                                                              |
| The NRC Resident Inspector was notified of this event by the licensee.       |
+------------------------------------------------------------------------------+
.+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   38432       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: HATCH                    REGION:  2  |NOTIFICATION DATE: 10/26/2001|
|    UNIT:  [] [2] []                 STATE:  GA |NOTIFICATION TIME: 23:03[EDT]|
|   RXTYPE: [1] GE-4,[2] GE-4                    |EVENT DATE:        10/26/2001|
+------------------------------------------------+EVENT TIME:        19:17[EDT]|
| NRC NOTIFIED BY:  JIM WATTS                    |LAST UPDATE DATE:  10/26/2001|
|  HQ OPS OFFICER:  JOHN MacKINNON               +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |R2 IRC TEAM MANAGER  R2      |
|10 CFR SECTION:                                 |                             |
|ARPS 50.72(b)(2)(iv)(B)  RPS ACTUATION - CRITICA|                             |
|AESF 50.72(b)(3)(iv)(A)  VALID SPECIF SYS ACTUAT|                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE  
|
+-----+----------+-------+--------+-----------------+--------+-----------------+
|                                                   |                          |
|2     A/R        Y       100      Power Operation  |0        Hot Shutdown     |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| AUTOMATIC REACTOR SCRAM. ALL RODS FULLY INSERT INTO THE CORE.                |
|                                                                              |
| Unit Two reactor scram.  The cause is presently under investigation.         |
| Preliminary indications are that the "B" Recirculation pump experienced a    |
| runback which was immediately followed by an increase to its previous speed, |
| resulting in a rapid reactor power increase causing the neutron monitoring   |
| system (Average Power Range Monitors) to trip and cause a reactor scram.     |
| All rods fully inserted into the core.  The following isolations occurred:   |
| Primary Containment isolated (Group 2 isolation), Secondary Containment      |
| isolation which started the Standby Gas Treatment System,  and Reactor Water |
| Clean-up isolated (Group 5 isoaltion).   HPCI and RCIC system initiated on   |
| low low reactor vessel water level, but did not inject into the reactor due  |
| to the feedwater system recovering reactor pressure vessel water level.  All |
| Emergency Core Cooling systems and the Emergency Diesel Generators are fully |
| operable if needed and the electrical grid is stable.                        |
|                                                                              |
| The NRC Resident Inspector was notified of this event by the licensee.       |
+------------------------------------------------------------------------------+
.
+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   38433       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: INDIAN POINT             REGION:  1  |NOTIFICATION DATE: 10/27/2001|
|    UNIT:  [2] [] []                 STATE:  NY |NOTIFICATION TIME: 04:24[EDT]|
|   RXTYPE: [2] W-4-LP,[3] W-4-LP                |EVENT DATE:        10/27/2001|
+------------------------------------------------+EVENT TIME:        02:08[EDT]|
| NRC NOTIFIED BY:  CARNAX                       |LAST UPDATE DATE:  10/28/2001|
|  HQ OPS OFFICER:  FANGIE JONES                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |JAMES TRAPP          R1      |
|10 CFR SECTION:                                 |                             |
|AINA 50.72(b)(3)(v)(A)   POT UNABLE TO SAFE SD  |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE  
|
+-----+----------+-------+--------+-----------------+--------+-----------------+
|2     N          N       0        Hot Shutdown     |0        Hot Shutdown     |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| TWO OF THREE AUXILIARY FEEDWATER PUMPS DECLARED INOPERABLE                   |
|                                                                              |
| The licensee reported that the auxiliary boiler (steam generator) feedwater  |
| pump 21 was declared inoperable at 0021 EDT due to high packing temperature  |
| during the planned plant shutdown.  Later at 0208 EDT, the second pump, 23,  |
| was declared inoperable because the outboard bearing could not be kept below |
| 200�F without the use of city water.  City water is not seismically          |
| qualified leading to the declaration of pump 23 being inoperable.  Pump 23   |
| is functional and able to provide feedwater.  Pump 22 is being used and is   |
| fully operational.  The plant is being cooled down as planned and due to the |
| pump problems has until 1400 EDT today, 10/27/01, to cool down to less than  |
| 350�F in accordance with technical specifications.  The licensee expects to  |
| meet the requirement with no trouble.                                        |
|                                                                              |
| The licensee has notified the NRC Resident Inspector.                        |
|                                                                              |
| ***** UPDATE FROM DENNIS CORNAX TO JOHN MACKINNON AT 2353 ON 10/28/01 ***** 
|
|                                                                              |
| The following text is a portion of a facsimile received from the licensee:   |
|                                                                              |
| "On October 27, 2001, at 0452, Indian Point Unit 2 exited the 12-hour action |
| statement of Technical Specification 3.4.B(1)b by achieving Hot Shutdown     |
| conditions with RCS temperature below 350�F.  23AFP remained in service for  |
| secondary side steam generator heat removal with City Water providing        |
| cooling to 23AFP's outboard bearing for the duration of the cooldown.  Cold  |
| Shutdown was achieved on October 27, 2001, at 1215."                         |
|                                                                              |
| "Although declared inoperable, preliminary evaluations by Engineering        |
| conclude that 21AFP would have been able to perform its safety function      |
| notwithstanding the high packing temperatures."                              |
|                                                                              |
| "A test of 23AFP was completed with preliminary indications that it too      |
| would have been able to perform its safety function without City Water       |
| cooling to the outboard bearing jacket cooler."                              |
|                                                                              |
| The licensee notified the NRC resident inspector.  The NRC operations        |
| officer notified the Region I Incident Response Center (Neil Perry) and NRR  |
| EO (William Beckner).                                                        |
+------------------------------------------------------------------------------+
.
+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   38435       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: SURRY                    REGION:  2  |NOTIFICATION DATE: 10/28/2001|
|    UNIT:  [1] [] []                 STATE:  VA |NOTIFICATION TIME: 01:05[EST]|
|   RXTYPE: [1] W-3-LP,[2] W-3-LP                |EVENT DATE:        10/28/2001|
+------------------------------------------------+EVENT TIME:        00:15[EDT]|
| NRC NOTIFIED BY:  ALLEN HARROW                 |LAST UPDATE DATE:  10/28/2001|
|  HQ OPS OFFICER:  LEIGH TROCINE                +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |BOB HAAG, REGION 2   IRC     |
|10 CFR SECTION:                                 |WILLIAM BECKNER      NRR     |
|ADEG 50.72(b)(3)(ii)(A)  DEGRADED CONDITION     |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE  
|
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          N       0        Refueling        |0        Refueling        |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| DISCOVERY OF APPARENT THROUGH-WALL INDICATIONS ON CONTROL ROD DRIVE    
     |
| MECHANISM PENETRATIONS                                                       |
|                                                                              |
| The following text is a portion of a facsimile received from the licensee:   |
|                                                                              |
| "Following shutdown for a scheduled refueling outage, Surry Unit 1 performed |
| a visual inspection of the reactor vessel control rod drive mechanism (CRDM) |
| penetrations per NRC Bulletin 2001-01."                                      |
|                                                                              |
| "At approximately 0015 on October 28, 2001, apparent through-wall            |
| indications were identified on CRDM penetrations 27 and 40.  The inspection  |
| is not yet complete.  This condition did not pose a significant safety risk  |
| during plant operation.  This is being reported as a non-emergency (8-hour   |
| report in accordance with 10 CFR 50.72(b)(3)(ii)(A) and                      |
| 50.73(a)(2)(ii)(A)."                                                         |
|                                                                              |
| The licensee stated that the unit is currently defueled.                     |
|                                                                              |
| The licensee notified the NRC resident inspector.                            |
+------------------------------------------------------------------------------+
.

Page Last Reviewed/Updated Thursday, March 25, 2021