Event Notification Report for October 16, 2001
U.S. Nuclear Regulatory Commission
Operations Center
Event Reports For
10/15/2001 - 10/16/2001
** EVENT NUMBERS **
38376 38388 38389 38390 38391
.
+------------------------------------------------------------------------------+
|General Information or Other |Event Number: 38376 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG: TEXAS DEPARTMENT OF HEALTH |NOTIFICATION DATE: 10/10/2001|
|LICENSEE: LAW ENGINEERING AND ENVIRONMENTAL SER|NOTIFICATION TIME:
17:29[EDT]|
| CITY: DALLAS REGION: 4 |EVENT DATE: 10/10/2001|
| COUNTY: STATE: TX |EVENT TIME: [CDT]|
|LICENSE#: L02453 AGREEMENT: Y |LAST UPDATE DATE: 10/10/2001|
| DOCKET: |+----------------------------+
| |PERSON ORGANIZATION |
| |LINDA HOWELL R4 |
| |C.W. (BILL) REAMER NMSS |
+------------------------------------------------+ |
| NRC NOTIFIED BY: JAMES H. OGDEN, JR. (fax) | |
| HQ OPS OFFICER: LEIGH TROCINE | |
+------------------------------------------------+ |
|EMERGENCY CLASS: NON EMERGENCY | |
|10 CFR SECTION: | |
|NAGR AGREEMENT STATE | |
| | |
| | |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| AGREEMENT STATE REPORT REGARDING DISCOVERY OF A LAW ENGINEERING AND
|
| ENVIRONMENTAL SERVICES GAUGE ON A RESIDENTIAL STREET BY AN EMPLOYEE
OF |
| ANOTHER COMPANY |
| |
| The following text is a portion of a facsimile received from the Texas |
| Department of Health, Bureau of Radiation Control: |
| |
| "Texas Incident No.: I-7810" |
| |
| "License No.: L02453" |
| |
| "Licensee: Law Engineering and Environmental Services, Houston, Texas (Fort |
| Worth Subsite)" |
| |
| "Event date and time: 10/10/01 a.m." |
| |
| "Event location: Dallas, Texas (exact location unknown at this time - gauge |
| was transported to 10722 North Stemmons Freeway, Dallas, Texas 75220[)]" |
| |
| "Event type: Found Nuclear Density Gauge, Troxler 3411 B, Serial #11251" |
| |
| "Notifications: Notified Troxler Electronic Labs, TDH Public Health Region |
| 3 to pickup gauge and have leak tested." |
| |
| "Event description: Gauge found in the middle of a residential street by an |
| employee of Giles Engineering, Texas License L04919-001. Gauge was found to |
| be un-locked - both case and control rod. The gauge was reported to be in |
| the 'On' position. No shipping papers were found in the case. No warning |
| stickers were reported to be on the exterior of the case. Troxler Labs |
| reports that the gauge was last seen by them over 2-years ago and was then |
| owned by Austin Testing Engineers - no evidence of Licensure through this |
| Agency. Gauge was tracked to Law Engineering in Fort Worth. TDH is holding |
| the gauge. Will have leak test performed. Licensee was unaware that the |
| gauge was missing and could not immediately find if the gauge was assigned |
| on a job for 10/10/01." |
| |
| "Transport vehicle description: None available at this time." |
| |
| "Media attention: None" |
| |
| (Contact the NRC operations officer for an agreement state point of |
| contact.) |
+------------------------------------------------------------------------------+
.
+------------------------------------------------------------------------------+
|General Information or Other |Event Number: 38388 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG: CALIFORNIA RADIATION CONTROL PRGM |NOTIFICATION DATE:
10/15/2001|
|LICENSEE: KRAZAN and ASSOCIATES |NOTIFICATION TIME: 13:02[EDT]|
| CITY: CLOVIS REGION: 4 |EVENT DATE: 10/11/2001|
| COUNTY: STATE: CA |EVENT TIME: [PDT]|
|LICENSE#: 4247-01 AGREEMENT: Y |LAST UPDATE DATE: 10/15/2001|
| DOCKET: |+----------------------------+
| |PERSON ORGANIZATION |
| |BILL JONES R4 |
| |BRIAN SMITH NMSS |
+------------------------------------------------+ |
| NRC NOTIFIED BY: KENT PRENDERGAST | |
| HQ OPS OFFICER: FANGIE JONES | |
+------------------------------------------------+ |
|EMERGENCY CLASS: NON EMERGENCY | |
|10 CFR SECTION: | |
|NAGR AGREEMENT STATE | |
| | |
| | |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| AGREEMENT STATE REPORT - STOLEN MOISTURE DENSITY GAUGE |
| |
| "Thursday, 10/11/01 a Krazan and Associates employee, after working late |
| took his portable moisture density gauge to his residence on Floyd Road in |
| Modesto, California. The gauge was reportedly locked and chained to the rear |
| of his pickup truck , but was not covered. The gauge chain was reportedly |
| cut and the gauge was stolen sometime between 9:00 PM and 6:00 AM on October |
| 12, 2001 by unknown persons. The gauge was a Troxler 3440 Serial Number |
| 231711 containing approximately 10 millicuries of cesium 137 and 40 |
| millicuries of americium 241. The RSO indicated he will be placing an ad in |
| the local newspaper offering a reward for the gauge. The RSO indicated that |
| he has counseled his employee for breaking company rules by taking the gauge |
| to his residence which is against company policy and California |
| regulations." |
+------------------------------------------------------------------------------+
.
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 38389 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: NINE MILE POINT REGION: 1 |NOTIFICATION DATE: 10/15/2001|
| UNIT: [] [2] [] STATE: NY |NOTIFICATION TIME: 13:16[EDT]|
| RXTYPE: [1] GE-2,[2] GE-5 |EVENT DATE: 10/15/2001|
+------------------------------------------------+EVENT TIME: 09:59[EDT]|
| NRC NOTIFIED BY: JOHN MANLY |LAST UPDATE DATE: 10/15/2001|
| HQ OPS OFFICER: FANGIE JONES +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: NON EMERGENCY |FRANK COSTELLO R1 |
|10 CFR SECTION: | |
|ACCS 50.72(b)(2)(iv)(A) ECCS INJECTION | |
|ARPS 50.72(b)(2)(iv)(B) RPS ACTUATION - CRITICA| |
|AESF 50.72(b)(3)(iv)(A) VALID SPECIF SYS ACTUAT| |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE
|
+-----+----------+-------+--------+-----------------+--------+-----------------+
| | |
|2 A/R Y 100 Power Operation |0 Hot Shutdown |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| AUTOMATIC REACTOR SCRAM DUE TO MAIN STEAM ISOLATION FOR UNKNOWN
CAUSE |
| |
| Unit 2 was operating at 100% power, steady state, when the Main Steam |
| Isolation Valves (MSIVs) fast closed causing a Reactor Protection System |
| (RPS) full scram, all rods fully inserted. The reactor feedwater pumps |
| tripped on Reactor Vessel Water Level 8 due to controlling reactor pressure |
| with Safety Relief Valves. After the feedwater trip, reactor pressure was |
| reduced to 550-650 psig so condensate booster pumps could inject to the |
| Reactor Pressure Vessel (RPV). At 1043 the Reactor Vessel Water Level 2 was |
| reached on the shrink from closure of the Safety Relief Valves. This in |
| turn caused a valid initiation and injection of the High Pressure Core Spray |
| (HPCS) and isolation of various containment isolation valves. |
| |
| Reactor vessel water level and pressure has been stabilized. HPCS has been |
| restored to standby. The plant is stable in Mode 3. The cause of the MSIV |
| isolation is still under investigation and a normal post scram review is |
| underway. |
| |
| The licensee notified the NRC Resident Inspector and will issue a media |
| release. |
+------------------------------------------------------------------------------+
.
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 38390 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: SEABROOK REGION: 1 |NOTIFICATION DATE: 10/15/2001|
| UNIT: [1] [] [] STATE: NH |NOTIFICATION TIME: 14:31[EDT]|
| RXTYPE: [1] W-4-LP |EVENT DATE: 10/15/2001|
+------------------------------------------------+EVENT TIME: 13:07[EDT]|
| NRC NOTIFIED BY: CHRISTOPHER O'CONNOR |LAST UPDATE DATE: 10/15/2001|
| HQ OPS OFFICER: FANGIE JONES +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: NON EMERGENCY |FRANK COSTELLO R1 |
|10 CFR SECTION: | |
|ARPS 50.72(b)(2)(iv)(B) RPS ACTUATION - CRITICA| |
|AESF 50.72(b)(3)(iv)(A) VALID SPECIF SYS ACTUAT| |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE
|
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 A/R Y 100 Power Operation |0 Hot Standby |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| AUTOMATIC REACTOR TRIP DURING PERFORMANCE OF QUARTERLY ROD
OPERABILITY |
| SURVEILLANCE |
| |
| The licensee reported that during a normal quarterly rod operability |
| surveillance an automatic reactor trip occurred, all rods fully inserted. |
| Preliminary investigation indicates that one rod dropped during rod motion |
| causing a negative rate trip to occur. |
| |
| The Emergency Feedwater system actuated, as expected on a reactor trip, and |
| is providing feedwater to the steam generators. Excess heat is being |
| rejected to the main condensers via the steam dumps. No safety or relief |
| valves opened during the transient. |
| |
| The plant is stable in Mode 3 and an investigation into the event is |
| underway. |
| |
| The licensee notified the NRC Resident Inspector and will issue a media |
| release. |
+------------------------------------------------------------------------------+
.
+------------------------------------------------------------------------------+
| |
|Fuel Cycle Facility |Event Number: 38391 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: PORTSMOUTH GASEOUS DIFFUSION PLANT |NOTIFICATION DATE:
10/15/2001|
| RXTYPE: URANIUM ENRICHMENT FACILITY |NOTIFICATION TIME: 16:34[EDT]|
| COMMENTS: 2 DEMOCRACY CENTER |EVENT DATE: 10/15/2001|
| 6903 ROCKLEDGE DRIVE |EVENT TIME: 10:30[EDT]|
| BETHESDA, MD 20817 (301)564-3200 |LAST UPDATE DATE: 10/15/2001|
| CITY: PIKETON REGION: 3 +-----------------------------+
| COUNTY: PIKE STATE: OH |PERSON ORGANIZATION |
|LICENSE#: GDP-2 AGREEMENT: N |ANTON VEGEL R3 |
| DOCKET: 0707002 |DON COOL NMSS |
+------------------------------------------------+ |
| NRC NOTIFIED BY: JIM McCLEERY | |
| HQ OPS OFFICER: FANGIE JONES | |
+------------------------------------------------+ |
|EMERGENCY CLASS: NON EMERGENCY | |
|10 CFR SECTION: | |
|NBNL RESPONSE-BULLETIN | |
| | |
| | |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| 24 HOUR REPORT - NRC BULLETIN 91-01 |
| |
| The following is a faxed report of finding in building X-330: |
| |
| During a building walk down, contaminated items in a category II staging |
| area were observed to be closer than the NCSA plant-048 allowed. The PSS |
| entered an anomalous condition. The items were moved to the appropriate |
| spacing requirements. The anomalous condition was exited. |
| |
| SAFETY SIGNIFICANCE OF EVENTS: |
| |
| The safety significance is low, The safe mass quantity is less than half of |
| the minimum critical mass, in a spherical geometry. and with optimum |
| moderation. The NCSE evaluated two items touching, these items were still |
| separated, had little moderation present, and are not spherical. |
| |
| POTENTIAL CRITICALITY PATHWAYS INVOLVED (BRIEF SCENARIO[S] OF HOW |
| CRITICALITY COULD OCCUR): |
| |
| In order for a criticality to occur more spacing violations, to increase |
| mass would have had to occur and additional moderating material would be |
| required. |
| |
| CONTROLLED PARAMETERS (MASS, MODERATION, GEOMETRY, CONCENTRATION,
ETC.): |
| |
| Mass and spacing are controlled. |
| |
| ESTIMATED AMOUNT, ENRICHMENT, FORM OF LICENSED MATERIAL (INCLUDE
PROCESS |
| LIMIT AND % WORST CASE OF CRITICAL MASS): |
| |
| Items involved were less than safe mass and enriched to 10% or less. |
| |
| NUCLEAR CRITICALITY SAFETY CONTROL(S) OR CONTROL SYSTEM(S) AND
DESCRIPTION |
| OF THE FAILURES OR DEFICIENCIES: |
| |
| The controls were mass and spacing. Spacing was the control violated. |
| |
| CORRECTIVE ACTIONS TO RESTORE SAFETY SYSTEM AND WHEN EACH WAS
IMPLEMENTED: |
| |
| The items observed inside the spacing requirements were moved to required |
| spacing requirements. |
| |
| The licensee notified the NRC Resident Inspector and the DOE representative. |
+------------------------------------------------------------------------------+
.