Event Notification Report for September 26, 2001

                    U.S. Nuclear Regulatory Commission
                              Operations Center

                              Event Reports For
                           09/25/2001 - 09/26/2001

                              ** EVENT NUMBERS **

38313  38314  38315  38316  

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   38313       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: SALEM                    REGION:  1  |NOTIFICATION DATE: 09/25/2001|
|    UNIT:  [1] [] []                 STATE:  NJ |NOTIFICATION TIME: 03:39[EDT]|
|   RXTYPE: [1] W-4-LP,[2] W-4-LP                |EVENT DATE:        09/24/2001|
+------------------------------------------------+EVENT TIME:        23:51[EDT]|
| NRC NOTIFIED BY:  JOSEPH PIERCE                |LAST UPDATE DATE:  09/25/2001|
|  HQ OPS OFFICER:  FANGIE JONES                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |JOHN KINNEMAN        R1      |
|10 CFR SECTION:                                 |                             |
|ARPS 50.72(b)(2)(iv)(B)  RPS ACTUATION - CRITICA|                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     M/R        Y       100      Power Operation  |0        Hot Standby      |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| MANUAL REACTOR TRIP DUE TO LOSS OF CIRCULATING WATER PUMPS                   |
|                                                                              |
| The licensee reported that Salem Unit 1 manually tripped the reactor due to  |
| a loss of circulating water pumps, caused by a fault on the #2 station power |
| transformer.  The fault isolation caused loss of one of the required two     |
| off-site power sources to both Salem units.  Auxiliary feedwater started on  |
| low steam generator level after isolation of main feedwater due to the       |
| reactor trip.  All system functioned as required.  The unit is stable in Hot |
| Standby and an investigation into the cause of the electrical disturbance is |
| underway.                                                                    |
|                                                                              |
| Two of four reactor coolant pumps tripped when the unit was tripped, which   |
| is expected with the partial loss of off-site power.  Presently, the only    |
| major secondary equipment that is unavailable is associated with the loss of |
| power to two of four non-vital 4 Kv buses.  There is one shutdown Technical  |
| Specification in effect and that is associated with having only one off-site |
| power source.                                                                |
|                                                                              |
| The licensee notified the NRC Resident Inspector.                            |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|General Information or Other                     |Event Number:   38314       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG:  DEFENSE MICROELECTRONICS ACTIVITY    |NOTIFICATION DATE: 09/25/2001|
|LICENSEE:  DEFENSE MICROELECTRONICS ACTIVITY    |NOTIFICATION TIME: 09:22[EDT]|
|    CITY:  McCLELLAN                REGION:  4  |EVENT DATE:        09/25/2001|
|  COUNTY:                            STATE:  CA |EVENT TIME:             [PDT]|
|LICENSE#:                        AGREEMENT:  Y  |LAST UPDATE DATE:  09/25/2001|
|  DOCKET:                                       |+----------------------------+
|                                                |PERSON          ORGANIZATION |
|                                                |GREG PICK            R4      |
|                                                |                             |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  DAVID PENTROSE               |                             |
|  HQ OPS OFFICER:  BOB STRANSKY                 |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          NON EMERGENCY         |                             |
|10 CFR SECTION:                                 |                             |
|NINF                     INFORMATION ONLY       |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| INCORRECT ACTIVITY SOURCE PROVIDED BY VENDOR                                 |
|                                                                              |
| The licensee called to report that a sealed source installed in their        |
| irradiator facility does not have the source activity specified. The source  |
| is supposed to contain 200 Ci, but the licensee estimates the actual         |
| activity at approximately 100 Ci. The source was installed by GE Vallecito   |
| within the past several weeks. The licensee has contacted GE regarding the   |
| apparent discrepancy.                                                        |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|General Information or Other                     |Event Number:   38315       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG:  NEW MEXICO RAD CONTROL PROGRAM       |NOTIFICATION DATE: 09/25/2001|
|LICENSEE:  BAKER HUGHES OIL FIELD OPERATIONS INC|NOTIFICATION TIME: 10:25[EDT]|
|    CITY:  HOBBS                    REGION:  4  |EVENT DATE:        09/22/2001|
|  COUNTY:                            STATE:  NM |EVENT TIME:        00:00[MDT]|
|LICENSE#:  WL241                 AGREEMENT:  Y  |LAST UPDATE DATE:  09/25/2001|
|  DOCKET:                                       |+----------------------------+
|                                                |PERSON          ORGANIZATION |
|                                                |GREG PICK            R4      |
|                                                |JOHN HICKEY          NMSS    |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  MILLER                       |                             |
|  HQ OPS OFFICER:  CHAUNCEY GOULD               |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          NON EMERGENCY         |                             |
|10 CFR SECTION:                                 |                             |
|NAGR                     AGREEMENT STATE        |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| BAKER HUGHES OIL FIELD OPERATIONS INC. REPORTED A STUCK WELL LOGGING SOURCE  |
|                                                                              |
| New Mexico state licensee Baker Hughes Oil Field Operations Inc. has a stuck |
| source 2018 ft below the surface which they are currently fishing for        |
| retrieval.  It contains 2 curies of Cesium-137, 18 curies                    |
| Americium-241/Beryllium and 0.8 microcuries Cesium-137.  The location is     |
| between Hobbs and Artesia, NM east of Loco Hills.                            |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Fuel Cycle Facility                              |Event Number:   38316       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: PORTSMOUTH GASEOUS DIFFUSION PLANT   |NOTIFICATION DATE: 09/25/2001|
|   RXTYPE: URANIUM ENRICHMENT FACILITY          |NOTIFICATION TIME: 13:28[EDT]|
| COMMENTS: 2 DEMOCRACY CENTER                   |EVENT DATE:        09/25/2001|
|           6903 ROCKLEDGE DRIVE                 |EVENT TIME:        09:30[EDT]|
|           BETHESDA, MD 20817    (301)564-3200  |LAST UPDATE DATE:  09/25/2001|
|    CITY:  PIKETON                  REGION:  3  +-----------------------------+
|  COUNTY:  PIKE                      STATE:  OH |PERSON          ORGANIZATION |
|LICENSE#:  GDP-2                 AGREEMENT:  N  |MONTE PHILLIPS       R3      |
|  DOCKET:  0707002                              |SUSAN FRANT          NMSS    |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  RITCHIE                      |                             |
|  HQ OPS OFFICER:  CHAUNCEY GOULD               |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          NON EMERGENCY         |                             |
|10 CFR SECTION:                                 |                             |
|NBNL                     RESPONSE-BULLETIN      |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| 4 HOUR 91-01 BULLETIN RESPONSE                                               |
|                                                                              |
| At 0930 uranium bearing material was observed in the interior spaces of a    |
| block wall in the X-705 recovery area the openings leading to the interior   |
| spaces of the block wall is a violation of administrative control #3 of NCSA |
| 0705_076.A03 because the exact geometry or volume of the potential           |
| collection area is unknown. This is a loss of one leg of double contingency  |
| as defined in NCSE 0705_076.E03. The presence of an unknown (at this time)   |
| amount of Uranium bearing material that was spilled (at some time in the     |
| facility's past) is a potential violation of passive design feature one of   |
| NCSA 0705_076.A03 which credits the physical integrity of X-705 system       |
| piping this would represent a loss of the second leg as defined in NCSE      |
| 0705_076.E03                                                                 |
|                                                                              |
| Measurements are being conducted and are ongoing to determine amount of      |
| material, which may affect this report.                                      |
|                                                                              |
|                                                                              |
|                                                                              |
| SAFETY SIGNIFICANCE OF EVENTS:                                               |
|                                                                              |
| The safety significance of this event is potentially high (at this time)     |
| because the exact amount of Uranium bearing material that could have entered |
| the opening in the block wall is unknown. Measurements to quantify the       |
| material are In progress. The apparent block wall construction (as evidenced |
| by visual inspection of wall openings in the other areas of Recovery)        |
| indicates the potential for the presence of unfavorable geometry voids       |
| within and between the blocks compromising the exterior building wall.       |
|                                                                              |
| POTENTIAL CRITICALITY PATHWAYS INVOLVED (BRIEF SCENARIO[S] OF HOW            |
| CRITICALITY COULD OCCUR):                                                    |
|                                                                              |
| If 1) a significant amount of uranium bearing material entered the void      |
| spaces of the block wall. 2) the material has collected in the multiple      |
| voids resulting in a single unfavorable geometry configuration. 3) the       |
| material has a high enrichment and uranium concentration, and 4) the         |
| material would become sufficiently moderated, then a potentially critical    |
| configuration could result. Note that no spills or leaks of uranium bearing  |
| material from present X-705 systems has occurred at this time. The material  |
| in question has apparently been there for some time.                         |
|                                                                              |
| CONTROLLED PARAMETERS (MASS. MODERATION, GEOMETRY, CONCENTRATION, ETC.):     |
|                                                                              |
| Double contingency for inadvertent Containers relies upon the physical       |
| integrity of X-705 piping to prevent a spill of an unsafe amount of          |
| material. An unsafe amount is defined by the concentration and enrichment of |
| the material. Double contingency also relies upon administrative controls    |
| limiting the presence of unfavorable geometry or unsafe volume containers    |
| that could collect a spill or leak.                                          |
|                                                                              |
| ESTIMATED AMOUNT. ENRICHMENT, FORM OF LICENSED MATERIAL (INCLUDE PROCESS     |
| LIMIT AND % WORST CASE OF CRITICAL MASS):                                    |
|                                                                              |
| Unknown at this time. Enrichment could be greater than 90% based upon        |
| historical operations. The form Is most likely uranyl nitrate or UO2F2.      |
| Measurements for determination of mass arid assay are currently in           |
| progress.                                                                    |
|                                                                              |
| NUCLEAR CRITICALITY SAFETY CONTROL(S) OR CONTROL SYSTEM(S) AND DESCRIPTION   |
| OF THE FAILURES OR DEFICIENCIES                                              |
|                                                                              |
| The openings leading to the interior spaces of the block wall is a violation |
| of administrative control #3 of NCSA.705_076.A03 because the exact geometry  |
| or volume of the potential collection area is unknown. This is a loss of one |
| leg of double contingency as defined in NCSE-0705_076.E03. The presence of   |
| an unknown (at this time) amount of uranium bearing material that has        |
| spilled (at some time in the facility's past) is a potential violation of    |
| passive design feature 1 of NCSA-0705_076.A03 which credits the physical     |
| integrity of  X-705 system piping. This would represent a loss of the second |
| leg of double contingency as defined in NCSE-0705_076,E03.                   |
|                                                                              |
| CORRECTIVE ACTIONS TO RESTORE SAFETY SYSTEM AND WHEN EACH WAS IMPLEMENTED:   |
|                                                                              |
| Samples of the material have been taken and DNA measurements will be taken   |
| to determine amounts of material and assay.                                  |
|                                                                              |
|                                                                              |
| The NRC Resident Inspector was notified and the DOE Representative will be   |
| notified.                                                                    |
+------------------------------------------------------------------------------+


Page Last Reviewed/Updated Thursday, March 25, 2021