Event Notification Report for April 6, 2000

                    U.S. Nuclear Regulatory Commission
                              Operations Center

                              Event Reports For
                           04/05/2000 - 04/06/2000

                              ** EVENT NUMBERS **

36855  36859  36864  36867  36868  36869  

!!!!!!!!! THIS EVENT HAS BEEN RETRACTED. THIS EVENT HAS BEEN RETRACTED  !!!!!!!
+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   36855       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: FARLEY                   REGION:  2  |NOTIFICATION DATE: 04/02/2000|
|    UNIT:  [1] [2] []                STATE:  AL |NOTIFICATION TIME: 07:25[EDT]|
|   RXTYPE: [1] W-3-LP,[2] W-3-LP                |EVENT DATE:        04/02/2000|
+------------------------------------------------+EVENT TIME:        05:05[CDT]|
| NRC NOTIFIED BY:  BILL ARENS                   |LAST UPDATE DATE:  04/05/2000|
|  HQ OPS OFFICER:  STEVE SANDIN                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |CAUDLE JULIAN        R2      |
|10 CFR SECTION:                                 |                             |
|DDDD 73.71               UNSPECIFIED PARAGRAPH  |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          N       0        Refueling        |0        Refueling        |
|2     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| 1 HOUR SECURITY REPORT                                                       |
|                                                                              |
| UNESCORTED PROTECTED AREA ACCESS GRANTED INAPPROPRIATELY.  IMMEDIATE         |
| COMPENSATORY MEASURES TAKEN.  THE LICENSEE WILL INFORM THE NRC RESIDENT      |
| INSPECTOR.                                                                   |
|                                                                              |
| CONTACT THE HEADQUARTERS OPERATIONS CENTER FOR ADDITIONAL DETAILS.           |
|                                                                              |
| * * * UPDATE 0955EDT ON 4/2/00 FROM VINCE MURPHY TO S.SANDIN * * *           |
|                                                                              |
| THE LICENSEE PROVIDED ADDITIONAL SPECIFIC INFORMATION.  A REVIEW WILL BE     |
| PERFORMED ON MONDAY 4/3 TO DETERMINE REPORTABILITY.  NOTIFIED R2DO           |
| (JULIAN).                                                                    |
|                                                                              |
| * * * RETRACTED AT 1420 EDT ON 4/5/00 BY VINCE MURPHY TO S. SANDIN * * *     |
|                                                                              |
| After review of the incident, it was determined that there was no improper   |
| unescorted protected area access granted, thus this event notification is    |
| retracted.                                                                   |
|                                                                              |
| The licensee notified the NRC Resident Inspector.  Notified R2DO (Steve      |
| Varley).                                                                     |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Research Reactor                                 |Event Number:   36859       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: GEORGIA INSTITUTE OF TECHNOLOGY      |NOTIFICATION DATE: 04/03/2000|
|   RXTYPE: 5000 KW RESEARCH HW                  |NOTIFICATION TIME: 10:49[EDT]|
| COMMENTS:                                      |EVENT DATE:        04/03/2000|
|                                                |EVENT TIME:        09:49[EDT]|
|                                                |LAST UPDATE DATE:  04/05/2000|
|    CITY:  ATLANTA                  REGION:  2  +-----------------------------+
|  COUNTY:  FULTON                    STATE:  GA |PERSON          ORGANIZATION |
|LICENSE#:  R-97                  AGREEMENT:  Y  |CAUDLE JULIAN        R2      |
|  DOCKET:  05000160                             |MARVIN MENDONCA  NRR PM      |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  ROD ICE                      |                             |
|  HQ OPS OFFICER:  CHAUNCEY GOULD               |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          N/A                   |                             |
|10 CFR SECTION:                                 |                             |
|DDDD 73.71               UNSPECIFIED PARAGRAPH  |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| SAFEGUARDS SYSTEM DEGRADATION RELATED TO DETECTION/MONITORING/ALARM          |
| FUNCTIONS..  COMPENSATORY MEASURES TAKEN IMMEDIATELY UPON DISCOVERY.         |
|                                                                              |
| CONTACT THE OPERATIONS CENTER FOR ADDITIONAL INFORMATION.                    |
|                                                                              |
| * * * UPDATE AT 1507 EDT ON 4/5/00 BY ROD ICE TO FANGIE JONES * * *          |
|                                                                              |
| Normal safeguards systems are restored.  Notified R2DO (Steve Cahill) and    |
| NRR (Ed Goodwin).                                                            |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   36864       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: NORTH ANNA               REGION:  2  |NOTIFICATION DATE: 04/04/2000|
|    UNIT:  [1] [2] []                STATE:  VA |NOTIFICATION TIME: 12:25[EDT]|
|   RXTYPE: [1] W-3-LP,[2] W-3-LP                |EVENT DATE:        04/04/2000|
+------------------------------------------------+EVENT TIME:        11:48[EDT]|
| NRC NOTIFIED BY:  MILTON MUNDEN                |LAST UPDATE DATE:  04/05/2000|
|  HQ OPS OFFICER:  FANGIE JONES                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |STEVE CAHILL         R2      |
|10 CFR SECTION:                                 |                             |
|ASHU 50.72(b)(1)(i)(A)   PLANT S/D REQD BY TS   |                             |
|ARPS 50.72(b)(2)(ii)     RPS ACTUATION          |                             |
|AESF 50.72(b)(2)(ii)     ESF ACTUATION          |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          N       0        Cold Shutdown    |0        Cold Shutdown    |
|2     M/R        Y       8        Power Operation  |0        Hot Standby      |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| LOSS OF RESERVE STATION TRANSFORMER CAUSED LOSS OF REACTOR COOLANT PUMP      |
| WHICH REQUIRED A REACTOR TRIP                                                |
|                                                                              |
| The 'C' reserve station transformer (RST) deenergized which resulted in a    |
| loss of the Unit 2 'C' reactor coolant pump (RCP).   The Unit 2 loss of RCP  |
| 'C' required a reactor trip, which was initiated manually, all rods fully    |
| inserted and the plant is stable in Hot Standby.  Unit 2 was on the steam    |
| dumps to the condenser and main feedwater at the time of the trip and        |
| continue on them.                                                            |
|                                                                              |
| Unit 1 '1H' emergency bus was lost due to the problem with the 'C' RST and   |
| the failure of the '1H' emergency diesel generator (EDG) to start.  The loss |
| of the '1H' bus caused the loss of the 'C' RCP and 'A' Residual Heat Removal |
| (RHR) pump, which led to the loss of core cooling circulation, but was       |
| restored in less than 2 minutes by starting the 'B' RHR pump.                |
|                                                                              |
| The 'C' RST and the '1H' EDG problems are being investigated, the cause of   |
| the problems are unknown at this time.  Unit 2 will remain in Hot Standby    |
| until all problems are corrected.                                            |
|                                                                              |
| The licensee informed the NRC Resident Inspector.                            |
|                                                                              |
| * * * UPDATE AT 1503 EDT ON 4/5/00 BY JIM CROSSMAN TO FANGIE JONES * * *     |
|                                                                              |
| The licensee made a correction to the reporting criteria.  Removed the       |
| original criteria of 10 CFR 50.72(b)(1)(ii) Degraded  Condition During       |
| Operation, this was for Unit 1 which was shutdown at the time.  Added the    |
| criteria 10 CFR 50.72(b)(2)(ii) ESF Actuation, due to a real start signal to |
| two of the emergency diesel generators.                                      |
|                                                                              |
| The licensee notified the NRC Resident Inspector.  Notified R2DO (Steve      |
| Cahill).                                                                     |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   36867       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: HATCH                    REGION:  2  |NOTIFICATION DATE: 04/05/2000|
|    UNIT:  [] [2] []                 STATE:  GA |NOTIFICATION TIME: 12:30[EDT]|
|   RXTYPE: [1] GE-4,[2] GE-4                    |EVENT DATE:        04/05/2000|
+------------------------------------------------+EVENT TIME:        09:38[EDT]|
| NRC NOTIFIED BY:  EDWIN URQUHART               |LAST UPDATE DATE:  04/05/2000|
|  HQ OPS OFFICER:  FANGIE JONES                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |STEVE CAHILL         R2      |
|10 CFR SECTION:                                 |                             |
|AESF 50.72(b)(2)(ii)     ESF ACTUATION          |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|                                                   |                          |
|2     N          N       0        Cold Shutdown    |0        Cold Shutdown    |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| TWO CONTAINMENT ISOLATION VALVES CLOSED DUE TO BLOWN FUSES                   |
|                                                                              |
| The Nuclear Safety and Compliance Group notified Operations today that a     |
| report of ESF activation should be made to the NRC.  The group noted that    |
| during the review of a logic system functional testing on diesel generator   |
| 2R43-S001A, a logic power fuse (2A71-F21A) blew closing two primary          |
| containment isolation valves (2G11-F003 & 2G11-F019).  These valves are the  |
| inboard drywell sump isolation valves.  This occurred on 4/2/00 at 0030      |
| EDT.                                                                         |
|                                                                              |
| The system was checked, fuses replaced, and the valves opened.  The valves   |
| are fully operational.                                                       |
|                                                                              |
| The licensee notified the NRC Resident Inspector.                            |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Other Nuclear Material                           |Event Number:   36868       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG:  U.S. NAVY                            |NOTIFICATION DATE: 04/05/2000|
|LICENSEE:  U.S. NAVY                            |NOTIFICATION TIME: 13:00[EDT]|
|    CITY:  YUMA                     REGION:  4  |EVENT DATE:        04/04/2000|
|  COUNTY:                            STATE:  AZ |EVENT TIME:        15:30[MST]|
|LICENSE#:  45-23645-01NA         AGREEMENT:  Y  |LAST UPDATE DATE:  04/05/2000|
|  DOCKET:                                       |+----------------------------+
|                                                |PERSON          ORGANIZATION |
|                                                |BILL JONES           R4      |
|                                                |STEVE CAHILL         R2      |
+------------------------------------------------+SCOTT MOORE          NMSS    |
| NRC NOTIFIED BY:  CDR. GARY HIGGINS            |                             |
|  HQ OPS OFFICER:  FANGIE JONES                 |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          N/A                   |                             |
|10 CFR SECTION:                                 |                             |
|BAB1 20.2201(a)(1)(i)    LOST/STOLEN LNM>1000X  |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| 500 mCi STRONTIUM/YTTRIUM SOURCE LOST TO LANDFILL                            |
|                                                                              |
| A generally licensed strontium/yttrium source, 500 mCi, from an 'In Flight   |
| Blade Inspection System' (IFBIS) was improperly placed in a dumpster which   |
| in turn was dumped at a regular land fill.  The U.S. Navy is investigating   |
| the incident and trying to determine where and how deep the source is in the |
| land fill.                                                                   |
|                                                                              |
| The U.S. Navy notified NRC Region 2 (M. Fuller) and intends to notify the    |
| State of Arizona.                                                            |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   36869       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: SOUTH TEXAS              REGION:  4  |NOTIFICATION DATE: 04/05/2000|
|    UNIT:  [1] [] []                 STATE:  TX |NOTIFICATION TIME: 14:38[EDT]|
|   RXTYPE: [1] W-4-LP,[2] W-4-LP                |EVENT DATE:        04/05/2000|
+------------------------------------------------+EVENT TIME:        12:52[CDT]|
| NRC NOTIFIED BY:  GERALD HILDEBRANDT           |LAST UPDATE DATE:  04/05/2000|
|  HQ OPS OFFICER:  FANGIE JONES                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |BILL JONES           R4      |
|10 CFR SECTION:                                 |                             |
|DDDD 73.71               UNSPECIFIED PARAGRAPH  |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          N       0        Refueling        |0        Refueling        |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| 1 HOUR SECURITY REPORT                                                       |
|                                                                              |
| Unescorted protected area access granted inappropriately.  Immediate         |
| compensatory measures taken.                                                 |
|                                                                              |
| The licensee notified the NRC Resident Inspector.                            |
|                                                                              |
| Contact the Headquarters Operations Center for additional details.           |
+------------------------------------------------------------------------------+


Page Last Reviewed/Updated Thursday, March 25, 2021